Chapter 6 Input and Output Specification
6-12
Expansion Module
Model
Specifications
G7E-TR10A
Output point
10 points
Insulation method
Photo coupler insulation
Rated load Voltage/current
DC12V/24V
Operating load voltage range
DC10.2 ~ 26.4V
Max. load current
0.5A/1 point, 4A/1COM
Current leakage when off
0.1mA or lower
Max. inrush current
4A/10ms or lower
Max. Voltage drop when on
DC 1.5V or lower
Surge Absorber
Clamp diode
Off
→
On
2 ms or lower
Response time
On
→
Off
2 ms or lower
Common method
10 points/ 1COM,
Operation indication
LED is on at on status of output
REMARK