Chapter 5 Power Supply / CPU
5-27
5.6.3 Direct I/O Operation function
This function is useful when reads an input relay’s state directly during execution of a program and uses in the operation, or
write the operation result directly to an output relay. Direct input/output is executed by the ‘IORF’ instruction. If this instruction is
used, the input/output image area will be directly updated and applied to the continuing operations.
REMARK
-. For detailed operation, refer to the ‘MASTER-K Manual for instruction’.
5.6.4 System error history
When the system is stopped by error occurrence, the CPU stores the error occurrence time and error code to the special data
register area. The most recent 16 error occurring times and error codes are stored in the special data register.
1) Special data register for error history
Data area
Description
D4901 ~ D4904
The 1
st
error information, The 17
th
error information
D4905 ~ D4908
The 2
nd
error information :
: :
Device
D4961 ~ D4964
The 16
th
error information
2) Description of each word
Data area
Contents
Description
D4900
H0001
Error occurred point
D4901
H0305
Year : 03, Month : 5
D4902
h2812
Date : 28, Hour : 12
D4903
h3030
Minute : 30, Second : 30
D4904
h0001
Error code (h0001)
3) Clear error data
Use a ‘data clear’ function of KGLWIN.
REMARK
Refer to the KGLWIN user’s Manual Chapter 7, for details.
Содержание MASTER-K 120S Series
Страница 26: ...Chapter 4 Names of Parts 4 3 2 K7M DRT60U 3 K7M DT60U 4 1 2 40 points main unit Standard 1 K7M DR40U ...
Страница 27: ...Chapter 4 Names of Parts 4 4 2 K7M DRT40U 3 K7M DT40U 4 1 3 30 points main unit Standard 1 K7M DR30U ...
Страница 28: ...Chapter 4 Names of Parts 4 5 2 K7M DRT30U 3 K7M DT30U 4 1 4 20 points main unit Standard 1 K7M DR20U ...
Страница 29: ...Chapter 4 Names of Parts 4 6 2 K7M DRT20U 3 K7M DT20U 4 1 5 30 points main unit Economic 1 K7M DR30UE ...
Страница 138: ...Chapter 7 Usage of Various Functions 7 54 c Program ...
Страница 306: ...Appendix 3 External Dimensions App3 2 2 Slim type G7E DC08A G7E RY08A G7F ADHB G7F DA2V G7F RD2A ...