Chapter 8 Communication Functions
8-65
3) Example program 2
It’s supposed that MASTER-K120S main unit is the master and it reads Coil Status of the station no. 17, a Modicon product.
The master reads status of the input contact 10197 ~ 10218 of the slave station no. 17.
The input contact of the slave station is supposed to be as follows and the data that are read is saved in M015.
Input
10220 10219 10218 10217
10216
10215
10214
10213
10212
10211 10210 10209
Status
X
X
1 1 0 1 0 1 1 1 0 1
Hex 3
5
D
Input
10208 10207 10206 10205
10204
10203
10202
10201
10200
10199 10198 10197
Status
1 0 1 1 1 0 1 0 1 1 0 0
Hex B
A
C
•
The status of input contact 10219,10220 are redundancy.
•
Data is sent starting from the low bit by byte unit. If the deficient bit of a byte is filled with 0. An example of sending the
above data is as follows.
Example 2) AC DB 35
① :
It designates slave station and function code ( No. of station : h11(17) , function code : h02 )
②
: Address setting
Address ‘0’ at MODBUS protocol means address ‘1’ actually .So if you want to designate address ‘10197’ ,
write address ‘10196’
③ :
Reading number setting ( Reading number is 22 from 10197 to 10220.)
④ :
This is MODBUS Communication instruction.
The data transmission starts lower byte. The remnant part of byte is filled with ‘0’
⑤
Stored data at D200,D201 are :
Device
Stored data
D200
h AC DB
D201
h 00 35
①
②
③
④
Содержание MASTER-K 120S Series
Страница 26: ...Chapter 4 Names of Parts 4 3 2 K7M DRT60U 3 K7M DT60U 4 1 2 40 points main unit Standard 1 K7M DR40U ...
Страница 27: ...Chapter 4 Names of Parts 4 4 2 K7M DRT40U 3 K7M DT40U 4 1 3 30 points main unit Standard 1 K7M DR30U ...
Страница 28: ...Chapter 4 Names of Parts 4 5 2 K7M DRT30U 3 K7M DT30U 4 1 4 20 points main unit Standard 1 K7M DR20U ...
Страница 29: ...Chapter 4 Names of Parts 4 6 2 K7M DRT20U 3 K7M DT20U 4 1 5 30 points main unit Economic 1 K7M DR30UE ...
Страница 138: ...Chapter 7 Usage of Various Functions 7 54 c Program ...
Страница 306: ...Appendix 3 External Dimensions App3 2 2 Slim type G7E DC08A G7E RY08A G7F ADHB G7F DA2V G7F RD2A ...