Chapter 7 Usage of Various Functions
7-70
2) Output Specification(P40, P41)
Signal Name
Rated load voltage
Load voltage range
Max. load current
Max. voltage drop during On
DC 12/24V
DC 10.2
∼
26.4V 100
㎃
≤
DC 0.3V
Forward direction
Reverse direction
Positioning
CW/Pulse
CCW/Directio
n
3) Names of wiring terminal
No.
Terminal No.
Name
Usage
①
P040
Positioning(Ch0)
Pulse output terminal
②
P041
Positioning(Ch1)
Pulse output terminal
③
P042
Direction pulse(Ch0)
Direction output terminal
④
P043
Direction pulse(Ch1)
Direction output terminal
⑤
COM0,COM1,COM2
Common Common
terminal
⑥
P
24V
External 24V supply terminal
Positioning function is sensitive to the external noise and should be handled with special care.
1) Be sure to use shielded twisted pair cables. Also provide Class 3 grounding
2) Do not run a twisted pair cable in parallel with power cables or other I/O lines which may generate noise
3) Before applying a power source for pulse generator, be sure to use a noise-protected power supply
⑤
⑤ ②
Pulse output
①
AC220V
FG COM0
P40
COM1
P41
COM2
P42
Direction pulse
Motor driver
Stepping motor
COM3
P43
P
COM
P44
⑥
③
⑤
④
Remark
Содержание MASTER-K 120S Series
Страница 26: ...Chapter 4 Names of Parts 4 3 2 K7M DRT60U 3 K7M DT60U 4 1 2 40 points main unit Standard 1 K7M DR40U ...
Страница 27: ...Chapter 4 Names of Parts 4 4 2 K7M DRT40U 3 K7M DT40U 4 1 3 30 points main unit Standard 1 K7M DR30U ...
Страница 28: ...Chapter 4 Names of Parts 4 5 2 K7M DRT30U 3 K7M DT30U 4 1 4 20 points main unit Standard 1 K7M DR20U ...
Страница 29: ...Chapter 4 Names of Parts 4 6 2 K7M DRT20U 3 K7M DT20U 4 1 5 30 points main unit Economic 1 K7M DR30UE ...
Страница 138: ...Chapter 7 Usage of Various Functions 7 54 c Program ...
Страница 306: ...Appendix 3 External Dimensions App3 2 2 Slim type G7E DC08A G7E RY08A G7F ADHB G7F DA2V G7F RD2A ...