Chapter 5 Power Supply / CPU
5-10
3) Integral
timer
In general, its operation is same as on-delay timer. Only the difference is the current value will not be clear when the
input condition of TMR instruction is turned off. It keeps the elapsed value and restart to increase when the input
condition is turned on again. When the current value reaches preset value, the timer output relay is turned on.
The current value can be cleared by the RST instruction only.
4)
Monostable timer
In general, its operation is same as off-delay timer. However, the change of input condition is ignored while the timer is
operating (decreasing). When current value reaches preset value the timer output relay is turned off and current value is
cleared.
Timer input condition
Timer output relay
Preset value
Current value
Timer reset input
Timer input condition
Timer output relay
Preset value
Current value
t0 t1
t2
t5
t1
t0
t2
t5+PT
t5
t3
PT = (t1-t0)+(t3-t2)
t4
t0
t1
t2
t3
t4
t0
t1
t2
t0+PT
t0
t2+PT
t2
t4+PT
t4
t4
Содержание MASTER-K 120S Series
Страница 26: ...Chapter 4 Names of Parts 4 3 2 K7M DRT60U 3 K7M DT60U 4 1 2 40 points main unit Standard 1 K7M DR40U ...
Страница 27: ...Chapter 4 Names of Parts 4 4 2 K7M DRT40U 3 K7M DT40U 4 1 3 30 points main unit Standard 1 K7M DR30U ...
Страница 28: ...Chapter 4 Names of Parts 4 5 2 K7M DRT30U 3 K7M DT30U 4 1 4 20 points main unit Standard 1 K7M DR20U ...
Страница 29: ...Chapter 4 Names of Parts 4 6 2 K7M DRT20U 3 K7M DT20U 4 1 5 30 points main unit Economic 1 K7M DR30UE ...
Страница 138: ...Chapter 7 Usage of Various Functions 7 54 c Program ...
Страница 306: ...Appendix 3 External Dimensions App3 2 2 Slim type G7E DC08A G7E RY08A G7F ADHB G7F DA2V G7F RD2A ...