Chapter 7 Usage of Various Functions
7-38
6) Error code list
(1) PID8AT
Error Code
Description
Corrective action
H0100
Scan time setting range error
Set scan time to available setting range
H0200
PV setting range error
Set PV setting to available setting range
H0300
SV setting range error
Set SV to available setting range SV
If PRC identification method is selected, check current PV is
less than SV.(SV should be greater than PV)
(2) PID8
Error Code
Description
Corrective action
H0100
Scan time setting range error
Set scan time to available setting range
H0200
Manual operation range error
Setmanual opration value to available setting range
H0300
Output limit value error(Min.)
Set minimum output limit value to available setting range and
Set it less than maximum output limit value
H0400
Output limit value error(Max.)
Set maximum output limit value to available setting range and
Set it greater than minimum output limit value
H0500
High frequency noise removal ratio setting error
Set this parameter to available setting range
H0600
Mode command set error
Available mode command set are P, PI, PID(PWM for each),
On-Off only.
H0700
PWM period setting error
Set PWM period to available setting range
H0800
P gain setting error
Set P gain period to available setting range
H0900
I time setting error
Set I time period to available setting range
H0A00
D time setting error
Set D time period to available setting range
H0B00
Bias setting error
Set Bias to available setting range
H0C00
PV setting range error
Set PV to available setting range
H0D00
SV setting range error
Set SV to available setting range
H0E00
SV Ramp setting error
Set SV Ramp to available setting range
H0F00
Delta MV setting error
Set Delta MV to available setting range
H1000
PID algorithm setting error
Check PID algorithm setting
H1100
Operation mode setting error
Available operation mode is 0 or 1
Содержание MASTER-K 120S Series
Страница 26: ...Chapter 4 Names of Parts 4 3 2 K7M DRT60U 3 K7M DT60U 4 1 2 40 points main unit Standard 1 K7M DR40U ...
Страница 27: ...Chapter 4 Names of Parts 4 4 2 K7M DRT40U 3 K7M DT40U 4 1 3 30 points main unit Standard 1 K7M DR30U ...
Страница 28: ...Chapter 4 Names of Parts 4 5 2 K7M DRT30U 3 K7M DT30U 4 1 4 20 points main unit Standard 1 K7M DR20U ...
Страница 29: ...Chapter 4 Names of Parts 4 6 2 K7M DRT20U 3 K7M DT20U 4 1 5 30 points main unit Economic 1 K7M DR30UE ...
Страница 138: ...Chapter 7 Usage of Various Functions 7 54 c Program ...
Страница 306: ...Appendix 3 External Dimensions App3 2 2 Slim type G7E DC08A G7E RY08A G7F ADHB G7F DA2V G7F RD2A ...