Chapter 7 Usage of Various Functions
7-36
c) operation
parameters
•
Scan time : S_TIME=5 (sampling time = 0.5 seconds)
•
Auto / Manual operation setting : Auto
•
Output limit : Max. = 4000, Min = 0
•
High frequency noise removal ratio : 10
•
SV setting : 1300(60
°
C ),1350(70
°
C ),1400(80
°
C ),1500(100
°
C)
•
Current value setting : D4780(Digital value of RTD module Ch0)
•
BIAS setting : 0 (If only P control is used, input proper value other 0)
•
EN_P, EN_I, EN_D setting : input proper values
•
PWM setting : If enabled, input proper values.
•
SV Ramp setting : Input proper values.
•
Delta MV setting : Input proper values.
•
PID Algorithm setting : Select proper algorithm.
d) RTD module setting
•
Channel setting : use channel 0
•
RTD Type setting : Pt100
•
Digital conversion data registration area : D4780
e) D/A module setting
•
Channel setting : use channel 0
•
output range setting: DC 4 ~ 20 mA
•
D/A conversion data registration area : D4980
As a result of PID8AT execution, Proportional gain(P),Derivative time(D),
Integral time(I) are stored D0102,D0103,D0104.
Содержание MASTER-K 120S Series
Страница 26: ...Chapter 4 Names of Parts 4 3 2 K7M DRT60U 3 K7M DT60U 4 1 2 40 points main unit Standard 1 K7M DR40U ...
Страница 27: ...Chapter 4 Names of Parts 4 4 2 K7M DRT40U 3 K7M DT40U 4 1 3 30 points main unit Standard 1 K7M DR30U ...
Страница 28: ...Chapter 4 Names of Parts 4 5 2 K7M DRT30U 3 K7M DT30U 4 1 4 20 points main unit Standard 1 K7M DR20U ...
Страница 29: ...Chapter 4 Names of Parts 4 6 2 K7M DRT20U 3 K7M DT20U 4 1 5 30 points main unit Economic 1 K7M DR30UE ...
Страница 138: ...Chapter 7 Usage of Various Functions 7 54 c Program ...
Страница 306: ...Appendix 3 External Dimensions App3 2 2 Slim type G7E DC08A G7E RY08A G7F ADHB G7F DA2V G7F RD2A ...