Chapter 8 Communication Functions
8-9
8.1.6 Execution of commands
1) Individual reading of device(R(r)SS)
(1) Introduction
This is a function that reads PLC device specified in accord with memory data type. Separate device memory can be read
up to 16 at a time.
(2) PC request format
Format name
Header
Station
No.
Command
Command
type
Number
of blocks
Device
length
Device name
Tail
Frame
check
Ex. of frame
ENQ
H20
R(r)
SS
H01
H06
%MW100
......
EOT BCC
ASCII value
H05
H3230 H52(72)
H5353 H3031
H3036
H254D57313030
H04
Item
Explanation
BCC
When command is lowercase(r), only one lower byte of the value resulted by adding 1 Byte
each to ASCII values from ENQ to EOT is converted into ASCII and added to BCC. For
example, the BCC of the above frame is gotten as below:
H05+H32+H30+H72+H53+H53+H30+H31+H30+H36+H25+H4D+H57+H31+H30+H30+H04
=H03A4 Therefore BCC value is A4.
Number of
Blocks
This specifies how much of the blocks composed of "[device length][device name]" are in this
request format. This can be set up to 16. Therefore, the value of [Number of blocks] must be
set between H01(ASCII value:3031)-H10(ASCII value:3030).
Device length
(Length of
device name)
This indicates the number of name's characters that means device, which is allowable up to 16
characters. This value is one of ASCII converted from hex type, and the range is from
H01(ASCII value:3031) to H10(ASCII value:3130). For example, if the device name is %MW0,
it has 4 characters to be H04 as its length. If %MW000 characters to be H06.
Device name
Address to be actually read is entered. This must be ASCII value within 16 characters, and in
this name, digits, upper/lower case, '%' only is allowable to be entered.
Remark
‘H’ of example frame represents hex value, and is unnecessary during preparing real frame.
1 block(setting can be repeated up to max. 16 blocks)
Содержание MASTER-K 120S Series
Страница 26: ...Chapter 4 Names of Parts 4 3 2 K7M DRT60U 3 K7M DT60U 4 1 2 40 points main unit Standard 1 K7M DR40U ...
Страница 27: ...Chapter 4 Names of Parts 4 4 2 K7M DRT40U 3 K7M DT40U 4 1 3 30 points main unit Standard 1 K7M DR30U ...
Страница 28: ...Chapter 4 Names of Parts 4 5 2 K7M DRT30U 3 K7M DT30U 4 1 4 20 points main unit Standard 1 K7M DR20U ...
Страница 29: ...Chapter 4 Names of Parts 4 6 2 K7M DRT20U 3 K7M DT20U 4 1 5 30 points main unit Economic 1 K7M DR30UE ...
Страница 138: ...Chapter 7 Usage of Various Functions 7 54 c Program ...
Страница 306: ...Appendix 3 External Dimensions App3 2 2 Slim type G7E DC08A G7E RY08A G7F ADHB G7F DA2V G7F RD2A ...