- 57 -
POWERLINK (LCBPOWERLINK only)
INSTRUMENT SETUP
-
(default: 1): set the instrument address
PC/PLC SETUP
The instrument works as
slave
in a POWERLINK network and features a dual port that allows to
exchange the weight and the main parameters with a POWERLINK
controller
. Load the xdd file
attached to the instrument to the development system and configure the device.
The data exchanged by the instrument are:
Output Data
from instrument (reading)
Addresses
Input Data
to instrument (writing)
Addresses
Gross weight
0x0000-0x0003 Command Register
0x0000-0x0001
Net weight
0x0004-0x0007 Digital outputs command
0x0002-0x0003
Exchange register R1
0x0008-0x000B Exchange register W1
0x0004-0x0007
Exchange register R2
0x000C-0x000D Exchange register W2
0x0008-0x0009
Status Register 1
0x000E-0x000F
Status Register 2
0x0010
Instrument status
0x0011
Execution register
0x0012-0x0013
Digital inputs status
0x0014
Digital outputs status
0x0015
STATUS LED
LED
Status
Description
L1
green
off
BUS IN - Ethernet link not established
on
BUS IN - Ethernet link established
blinking
BUS IN - Ethernet activity detected
L3
red
on
communication error
L4
green
off
initialization status
blinking
stop status
single blinking
Pre-Operational 1 status
double blinking
Pre-Operational 2 status
triple blinking
ReadyToOperate status
on
Operational status
L5
green
off
BUS OUT - Ethernet link not established
on
BUS OUT - Ethernet link established
blinking
BUS OUT - Ethernet activity detected