- 43 -
IS = 15
It is activated if, at batching start, the formula recalled for running
exceeds the maximum weight.
It is activated in the sample weight setting, in real calibration, after
the fifth sample weight value has been entered.
It’s not possible to display properly the number because is greater
than 999999 or less than -999999.
IS = 19
The batching is cancelled. If the alarm persists, contact technical
assistance.
IS = 5
The batching is paused.
IS = 13
The batching data were not read remotely.
It is activated for 3 seconds if you try to stop the batching (by
closing the related input) when the START input is closed. Open
the START input to cancel the alarm.
EXR = 0xFFFF
Weight too high: zero setting not possible.
IS = 17
It is activated if, at batching start, the weight on the scale is higher
than the minimum set in constants (
).If the weight comes back
below to the minimum set, the batching starts.
IS = 8
It is activated if at batching end the weight is different from the
value set in formula by a value higher than tolerance.
IS = 6
It is activated, during the unload (cycle end contact closed), when
the product is not extracted. It is automatically cancelled if the
product decreases.
With an alarm the relays open and the analog outputs go to the lowest possible value
according to the following table:
RANGE
0÷20 mA
4÷20 mA
0÷5 V
0÷10 V
Output value
0 mA
3.5 mA
0 V
0 V