- 55 -
MODBUS/TCP (LCBMODBUSTCP only)
INSTRUMENT SETUP
-
(default:
): it allows to select the reading/writing of the byte in LITTLE-ENDIAN or BIG-
ENDIAN mode
-
: LITTLE ENDIAN
-
: BIG ENDIAN
-
(default: 10.2.0.170): set instrument IP address
-
(default: 255.255.255.0): set instrument Subnet Mask
-
(default: 0.0.0.0): set Gateway address of Ethernet network
In order to apply the changes, press until the display shows
.
PC/PLC SETUP
The instrument works as
slave
in a Modbus/TCP network and features a dual port that allows to
exchange the weight and the main parameters with a Modbus/TCP
master
. Use port 502 for the
communication.
The supported Function Codes are:
-
04: Read Input Registers
-
06: Preset Single Register
-
16: Preset Multiple Registers
The data exchanged by the instrument are:
Output Data
from instrument (reading)
Addresses
Input Data
to instrument (writing)
Addresses
Gross weight
0x0000-0x0003 Command Register
0x0000-0x0001
Net weight
0x0004-0x0007 Digital outputs command
0x0002-0x0003
Exchange register R1
0x0008-0x000B Exchange register W1
0x0004-0x0007
Exchange register R2
0x000C-0x000D Exchange register W2
0x0008-0x0009
Status Register 1
0x000E-0x000F
Status Register 2
0x0010
Instrument status
0x0011
Execution register
0x0012-0x0013
Digital inputs status
0x0014
Digital outputs status
0x0015