- 31 -
COMMUNICATION INTERFACE
BCR (BATCHING CONFIGURATION REGISTER)
Bit 7
Bit 6
Bit 5÷4
Bit 3
Bit 2
Bit 1
Bit 0
not used
not used
0 -
1 -
0
00 – not used
01 -
10 -
11 -
0
0 -
1 -
0 -
1 -
0 -
1 -
WRITING
READING
Write the BCR value in W1.
Send command 1133 to CMDR.
Send command 1132 to CMDR.
Read the OCR value in R1.
Examples: operation settings configuration
OCR CONTENTS
PARAMETERS CONFIGURATION
Binary
Hexadecimal
Decimal
00010010
0x12
018
1
10110001
0xB1
177
3
10100110
0xA6
166
2
PROGRAMMING OF BATCHING CONSTANTS
From the weight displaying press
, then press to display
and
confirm (see section
BATCHING CONSTANTS (LOAD program)
).
WARNING
: the time values of the batching constants are expressed in tenths of a second.
Example: to set up
to 10.2 seconds via the communication interface, write 102 in W1 and send
command 1005 to CMDR.
MINIMUM WEIGHT
(from 0 to full scale; default: 10): minimum weight, value at which the scale is considered
empty. Batching start is only allowed if the weight is lower than this value, during the unloading
phase the CYCLE END contact will be opened when the weight reaches this value and after the
safe emptying time is over.