Standards and guidelines
Required Markings
For installation on industrial machines in accordance with the Standard for Industrial Machinery
NFPA79 only
Maximum Ambient Temperature:
Electronic Adapter Ambient
INV MA 4 1.5
ADP MA WDM
35°C
INV MB 4 2.2
ADP MB WDM
45°C
INV MB 4 3.0
ADP MB WDM
40°C
INV MB 4 4.0
ADP MB WDM
35°C
INV MC 4 5.5
ADP MC WDM
40°C
INV MC 4 7.5
ADP MC WDM
35°C
Internal Overload Protection Operates within 60 seconds when reaching 150% of the Motor
Full Load Current.
Suitable for use on a circuit capable of delivering not more than 5kA rms symmetrical amperes,
400 Volts maximum when protected by fuses.
Integral solid state short circuit protection does not provide branch circuit protection. Branch cir-
cuit protection must be provided in accordance with the Manufacturer Instructions, National
Electrical Code and any additional local codes.
All wiring terminals marked to indicate proper connections for the power supply, load and con-
trol circuitry.
Instruction for operator and servicing instructions on how to mount and connect the products
using the intended motor connection adapter
Use 75oC copper wires only.
Connection of external motor overtemperature sensing is required.