31
5.4
Start-up steps
Parameterising is possible prior to installation.
Parameterisation can be performed before the drive control is installed in the engine.
The drive control has a 24 V low-voltage input for this purpose, which can supply the electric
system without requiring mains power.
The start-up can be performed using a PC communication cable USB at plug M12 with inte-
grated interface converter RS485/RS232 (article no. 10023950) or using the INVEOR manual
control unit MMI with connection cable RJ11 at plug M12 (article no. 10004768).
Start-up using the PC:
Install the KFU-tronic pc software (you can obtain programming software from your sup-
plier free of charge).
Connect the PC to the M12 plug M1 with the optional connection cable.
Load or determine the motor data record (parameters 33,030 to 33,050); it may be neces-
sary to optimise the speed control (parameters 34,100 to 34,101).
Make the application settings (ramps, inputs, outputs, target values etc.).
Optional: Define an access level (1 – MMI, 2 – user, 3 – manufacturer).
In order to ensure an ideal operating structure for the PC software, the parameters are classified
into different access levels. There are the following levels:
1.
Manual control unit: – the drive control is programmed using the manual control unit
2.
User: – the basic parameters can be programmed into the drive control using the PC
software
3.
Manufacturer:
o
an extended selection of parameters can be programmed into the drive control using
the PC software