KFU-
tronic
46
3.070
PID stand-by time
Unit: s
min: 0
max.: 10000
Parameter manual:
S. xy
Transfer status:
2
def.: 0
own value (to
be entered!)
Relationship to
parameter:
1,020
If the drive control operates the set time with the low speed (parameter
1,020), the motor is stopped (0 Hz), see also Chapter 5.2.1, “PID process
control”
0
= disable
3.071
PID stand-by hysteresis
Unit: %
min: 0
max.: 50
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (to
be entered!)
Relationship to
parameter:
3,060
Condition for waking up the PID controller from stand-by.
Once the control difference exceeds the set value in %, the control begins
6.3.5
Analogue inputs
For analogue inputs 1 and 2 (Alx display Al1/Al2)
4.020/4.050
Alx reference type
Unit: integer
min: 1
max.: 2
Parameter manual:
p. xy
Transfer status:
2
def.: 1
own value (to
be entered!)
Relationship to
parameter:
Function of analogue inputs 1/2:
1 = voltage input
4.021/4.051
Alx minimum input
Unit: %
min: 0
max.: 100
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (to
be entered!)
Relationship to
parameter:
Specifies the minimum value of the analogue inputs as a percentage of the
final area value.
Example:
0…10 V or 0…20 mA = 0%…100%
Содержание KFUtronic Series