40
1.131
Enable software
Unit: integer
min: 0
max.: 11
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (to
be entered!)
Relationship to
parameter:
1,132
1,150
2,050
4,030
4,050
WARNING
The motor may start immediately, depending on the change made.
Selection of the source for the control release.
0 = digital input 1
1 = digital input 2
2 = digital input 3
3 = digital input 4
4 = analogue input 1 (has to be selected in parameter 4.030)
5 = analogue input 2 (has to be selected in parameter 4.050)
6 = fieldbus
7 = SAS
8 = digital input 1 right / digital input 2 left
1,150 must be set to “0”
9 = autostart:
10 = KFU-tronic Soft-PLC
11 = preset frequency input (all inputs which are selected in parameter
2,050)
The motor may start immediately if hardware is enabled (En.Hw. Fig. 8)
and a reference have been provided.
1.132
Start protect
Unit: integer
min: 0
max.: 6
Parameter manual:
p. xy
Transfer status:
2
def.: 1
own value (to
be entered!)
Relationship to
parameter:
1,131
Selection of the behaviour in response to enable software (parameter
1,131).
No effect if autostart was selected.
0 = immediate start when high signal is received at start input of control re-
lease
1 = start only in case of rising shoulder at start input of control release
2 = digital input 1 (function active at high signal)
3 = digital input 2 (function active at high signal)
4 = digital input 3 (function active at high signal)
5 = digital input 4 (function active at high signal)
Содержание KFUtronic Series