Motorized potentiometer
This mode must be selected in the parameter 1.130. This function can be used as a source of
target values for the frequency setting mode as well as for the PID process controller.
2.150
MOP digital Input
unit: integer
min: 0
max.: 7
Parameter manual:
p. xy
Transfer status:
2
def.: 3
Own value (to
be entered!)
Relationship to
Parameter:
1,130
4,030
4,050
Selection of the source for increasing and reducing the target value
0 = Digital In 1 + / Digital In 2 -
1 = Digital In 1 + / Digital In 3 -
2 = Digital In 1 + / Digital In 4 -
3 = Digital In 2 + / Digital 3 -
4 = Digital In 2 + / Digital In 4 -
5 = Digital In 3 + / Digital In 4 -
6 = Analogue In 1 + / Analogue In 2 -
(must be selected in parameter 4,030 / 4,050)
7 = reference from KFU-tronic Soft-PLC
2.151
MOP step range
Unit: %
min: 0
max.: 100
Parameter manual:
p. xy
Transfer status:
2
def.: 1
Own value (to
be entered!)
Relationship to
parameter:
1.020
1.021
Increments at which the target value changes per keystroke.
2.152
MOP step time
Unit: s
min: 0.02
max.: 1000
Parameter manual:
p. xy
Transfer status:
2
def.: 0.04
Own value (to
be entered!)
Relationship to
parameter:
Indicates the time in which the target value totals up for permanent signal.
2.153
MOP response time
Unit: s
min: 0.02
max.: 1000
Parameter manual:
p. xy
Transfer status:
2
def.: 0.3
Own value (to
be entered!)
Relationship to
parameter:
Indicates the time for which the signal is considered permanent.