KFU-
tronic
20
The standard adapter plate is an adapter plate whose underpart has not been
refinished. There are no boreholes.
Individual tailored adapter plates for selected motors are available from your KFU-tronic. sup-
plier
5.
Adjust the adapter plate (1) by creating the appropriate boreholes (2) for
attachment to the motor.
The contractor starting up the device is responsible for complying with the protection
category when sealing the adapter plate on the motor.
In case of questions, please contact your usual contact person at you KFU-tronic supplier.
6.
Place the seal (3).
7.
Lead the motor connection line past the connection terminal and through the adapter
plate; attach the adapter plate to the motor with the four fastening bolts (4) (torque: 2.0 Nm).
8.
Attach the engine wires in the correct circuit, see also Fig. 4. (torque: 3,0 Nm).
When installing the engine wires, ensure that all bolts on the terminal board are used
with the nuts provided, even if the star point is not connected!
Electric jumper
1
2
9.
If a motor PTC/Klixxon is available, wire the connection cables to
terminals T1 and T2 (1) (torque: 0.6 Nm).
Make sure during assembly that the connection cables are not trapped.
If the motor has a temperature sensor, this has to be connected to terminals
T1 and T2 (1); this requires that the electric jumper (2) fitted in the delivery state
has to be removed.
If the electric jumper is installed, the temperature of the motor will not be monitored.
10.
Plug the drive control onto the adapter plate and fasten it evenly using the
four lateral bolts (torque: 4.0 Nm).
Содержание KFUtronic Series
Страница 5: ...KFU tronic 4 ...
Страница 31: ...KFU tronic 30 5 3 Block diagram General structure of target value generation ...