6.4.3 Menu "C setup"
Function
Setting / Description
C1 process input
C1.1 calibration
C1.1.1 zero calibration
Display of actual zero calibration value.
Query: calibrate zero?
Select: break (return with
^
key) / standard (factory setting) / manual (display last
value, set new value, range: -1.00
…
+1 m/s) / automatic (shows the current value as
the new zero calibration value)
C1.1.2 size
Select from size table.
C1.1.3 GKL
Set value acc. to the information on the nameplate.
Range: 0.5
…
20
C1.1.4 measurement
Select: volume flow (default setting) / mass flow (using the fixed density, the volume
flow is converted into mass flow)
C1.1.5 range
Measuring range for the analogue outputs (current output, frequency output and
display).
Range: 0.0
…
100%
C1.1.6 density
For calculating the mass flow from the volume flow.
Range: 0.1
…
5 kg/L
C1.1.7 target conduct.
Reference value for on-site calibration.
Range: 1.000...50000
μ
S/cm
C1.1.8 EF electr. factor
For calculation of the conductivity based on the electrode impedance.
Query: calibrate EF?
Select: break (return with
^
key) / standard (with factory setting) / manual (set
desired value) / automatic (determines EF according to the setting in C1.1.10)
C1.1.9 field frequency
Setting as on flow sensor nameplate = line frequency x value (from the following
list): 1/2; 1/4; 1/6; 1/8; 1/12; 1/18; 1/36; 1/50
C1.1.10 select settling
Select settling (special function).
Select: standard (fixed allocation) / manual (manual time setting for the settling
time for the field current)
C1.1.11 settling time
Only available if "manual" is selected in C1.1.10.
Range: 1.0
…
250 ms
C1.1.12 line frequency
Setting the line frequency.
Select: 50 Hz or 60 Hz
C1.1.13 act. coil resistance
Display of the actual resistance of the field coil.