OPERATION
6
57
IFC 050
www.krohne.com
09/2016 - 4002184003 - MA IFC 050 R03 en
C2.3 pulse output D
C2.3.1 pulse shape
Specify the pulse shape.
Select: symmetric (about 50% on and 50% off) / automatic (constant pulse with
about 50% on and 50% off at max. pulse rate) / fixed (fixed pulse rate, for setting
refer to "C2.3.3 max. pulse rate")
C2.3.2 pulse width
Only available if set to "fixed" in C2.3.1.
Range: 0.05
…
2000 ms
Note: max. setting value Tp [ms]
≤
500 / max. pulse rate [1/s], gives the pulse
width = time where the output is activated
C2.3.3 max. pulse rate
Setting the maximum pulse rate.
Limit is 120% of this pulse rate.
C2.3.4 pulse value unit
Selection of the unit from a list, depending on the "measurement".
C2.3.5 value p. pulse
Set value for volume or mass per pulse.
xxx.xxx, measured value
C2.3.6 polarity
Set polarity; please note flow direction in C1.2.2!
Select: both polarities (plus and minus values are displayed) / positive polarity
(display for negative values = 0) / negative polarity (display for positive values = 0) /
absolute value (always displays positive, with both negative and positive values)
C2.3.7 invert signal
Select: off (activated output: switch closed) / on (activated output: switch open)
C2.3.8 information
Serial number of the I/O board, software version number and production date of the
circuit board.
C2.3.9 simulation
For sequence refer to "B1.3 pulse output D".
C2.3 status output D
C2.3.1 mode
Measuring conditions of the output.
Select: out of specification (output set, signals status of category "error in device"
or "application error" or "out of specification" refer to
Status messages and
diagnostic information
on page 63) /
application error (output set, signals status of the category "error in device" or
"application error" refer to
Status messages and diagnostic information
on page
63) /
polarity flow (polarity of the current flow) /
over range flow (over range of the flow) /
counter 1 preset (activates counter 1 when preset value is reached) /
counter 2 preset (activates counter 2 when preset value is reached) /
output A (displays the polarity at output A) /
off (switched off) /
empty pipe (when pipe empty, output activated) /
error in device (output set, signals status of the category "error in device" refer to
Status messages and diagnostic information
on page 63)
C2.3.2 invert signal
Select: off (activated output: switch closed) / on (activated output: switch open)
C2.3.3 information
Serial number of the I/O board, software version number and production date of the
circuit board.
C2.3.4 simulation
For sequence refer to "B1.3 status output D".