4
ELECTRICAL CONNECTIONS
26
IFC 050
www.krohne.com
09/2016 - 4002184003 - MA IFC 050 R03 en
4.4.6 Preparing field current cable C, connection to flow sensor
•
The field current cable is not part of the scope of delivery.
•
The shield is connected in the terminal compartment of the flow sensor directly via the shield
and a clip.
•
Bending radius:
≥
50 mm / 2"
Required materials
•
Shielded 2-wire insulated copper cable
•
Insulating tube, size according to the cable being used
•
Heat-shrinkable tubing
•
Wire end ferrules to DIN 46 228: size according to the cable being used
1
Strip the conductor to dimension a.
2
Trim the outer shield to dimension b and pull it over the outer sheath.
3
Crimp wire end ferrules onto both conductors.
4
Pull a shrinkable tube over the prepared cable.
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
Figure 4-6: Preparation of field current cable C
a = 50 mm / 2"
b = 10 mm / 0.4"