4
ELECTRICAL CONNECTIONS
20
IFC 050
www.krohne.com
09/2016 - 4002184003 - MA IFC 050 R03 en
4.4 Preparing the signal and field current cables
4.4.1 Signal cable A (type DS 300), construction
•
Signal cable A is a double-shielded cable for signal transmission between the flow sensor
and signal converter.
•
Bending radius:
≥
50 mm / 2"
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
Figure 4-1: Construction of signal cable A
1
Stranded drain wire (1) for the inner shield (10), 1.0 mm
2
Cu / AWG 17 (not insulated, bare)
2
Insulated wire (2), 0.5 mm
2
Cu / AWG 20
3
Insulated wire (3), 0.5 mm
2
Cu / AWG 20
4
Outer sheath
5
Insulation layers
6
Stranded drain wire (6) for the outer shield (60)