4
ELECTRICAL CONNECTIONS
18
IFC 050
www.krohne.com
09/2016 - 4002184003 - MA IFC 050 R03 en
4.3 Electrical cables for remote device versions, notes
4.3.1 Notes on signal cable A
Observe the following notes:
•
Lay the signal cable with fastening elements.
•
It is permissible to lay the signal cable in water or in the ground.
•
The insulating material is flame-retardant to EN 50265-2-1: 1997 and IEC 60322-1-2: 2005.
•
The signal cable does not contain any halogens and is unplasticized, and remains flexible at
low temperatures.
•
The connection of the inner shield (10) is carried out via the stranded drain wire (1).
•
The connection of the outer shield (60) is carried out via the stranded drain wire (6).
4.3.2 Notes on field current cable C
INFORMATION!
Signal cable A (type DS 300) with double shield ensures proper transmission of measured
values.
DANGER!
A shielded 2-wire copper cable is used for the field current cable. The shielding MUST
MUST
MUST
MUST be
connected in the housing of the flow sensor and signal converter.
INFORMATION!
The field current cable is not part of the scope of delivery.