1.
Wire the AC plug supplied for the selected external conductors. For
more detailed information, refer to the website of the plug manufac‐
turer under
www.wieland-electric.com
. Do not yet close the AC plug.
2.
Connect one of the two connected phases to PE at the inverter side.
Make this connection inside the AC plug or use an external junction
box, as shown in
3.
Close the AC plug.
Fig. 8:
Connection of N and PE in the AC plug (above) or junction box
(below)
①
Connection cable between N and PE with the connection point inside
the AC plug
②
External conductor L1
③
External conductor L2
④
Connection cable between N and PE with the connection point inside
the junction box
⑤
Casing of the AC plug
⑥
Junction box
Fig. 9:
External conductor voltages in 2- and 3-phase grids with
100 V ... 127 V
Installation
11/2017 | DOC01664604 | KOSTAL operating instructions PIKO inverter 1.5 - 4.2 MP
35