The inverter output power can be manually limited to a minimum of 500 W.
When the power is manually limited, the
Power reduction
symbol is shown
in the status display and the
„Derating“
/
„Cause: User default“
measure‐
ment is displayed.
The device can regulate the input voltage to a manually adjustable value.
This switches off the automatic setting of the MPP (MPP tracking). The
input voltage can be adjusted over a range between the maximum and
minimum input voltage and the minimum input voltage in 1V steps.
Exemplary application: Hydroelectric installation
NOTICE!
Before setting a fixed input voltage, make sure that the PV
generator is suitable for this. Otherwise, this may result in
yield losses or damage to the system.
After the country setting has been deleted the device restarts anew and
displays the guided 1st commissioning menu.
Resetting the device to the factory setting deletes the following data:
n
Yield data
n
Event messages
n
Date and time
n
Country setting
n
Display language
n
Network settings
After the factory setting has been deleted, the device restarts anew and
displays the guided 1st commissioning menu.
Power limiter
Fixed voltage
Delete country setting
Factory setting
Structure and function