1.
Grasp the inverter by the recesses
①
position it
②
in the middle of
the mounting plate
➊
and press lightly (example in Fig. left).
2.
Lower the inverter
③
until the securing sheet metal element of the
mounting plate audibly locks in place. In this process, the hooks on
the rear of the inverter must be guided above the catches on the
mounting plate.
3.
The inverter must now be firmly seated on the mounting plate and it
can no longer be lifted (upwards).
NOTICE!
How to remove the inverter from the mounting plate is
described under
Chapter 4.11 „Deinstalling the
4.3 Prepare AC connection
4.3.1 Miniature circuit breaker
Information on the required line circuit breaker and the cables to be used
between the inverter and the line circuit breaker is provided in
Chapter 9.2 „AC cables and line circuit breakers“ on page 73
4.3.2 Fault current circuit breaker
If the local installation regulations require the installation of an external
residual current circuit breaker, then a Type A residual current circuit
breaker as per IEC 62109-1, § 7.3.8. is sufficient.
Attaching the inverter on
the mounting plate
Installation
11/2017 | DOC01664604 | KOSTAL operating instructions PIKO inverter 1.5 - 4.2 MP