AKD Installation | 7 Technical description and data
7.14.2.4 Switch-off behavior in the event of a fault
The behavior of the drive always depends on the fault type and the setting of a number of dif-
ferent parameters (DRV.DISMODE, VBUS.UVFTHRESH, CS.VTHRESH, and others; see
the
WorkBench Online Help
for more details).See the
Drive Fault and Warning Messages
and Remedies
section of the
WorkBench Online Help
for a table describing the specific beha-
vior of each fault.
The follwing pages show examples for the possible fault behaviors.
Switch-off behavior for faults that cause an immediate power stage disable
This is a category 0 stop according to IEC 60204 (
If velocity drops below threshold
CS.VTHRESH
or timeout occurs the motor holding brake is
applied (
# 118). Set parameter MOTOR.BRAKEIMM to 1 with vertical axes, to apply the
motor holding brake immediately after faults.
50
Kollmorgen | kdn.kollmorgen.com | October 2017