TS_619_00 PW9000DPA S2 User Manual 13/3/17
59
8: Specification
8.6
Environmental
Module Type
DPA 30
DPA 40
DPA 50
Audible Noise with 100% / 50% Load
dBA
70 / 63
74 / 67
76 / 69
Operation temperature
°C
0 to +40
Ambient Temperature for Batteries
°C
+20 to +25 (recommended)
Storage Temperature
°C
-25 to +70
Battery Storage Time at Ambient Temperature
Max. 6 months
Max. altitude (above sea level)
m
1000m (3300ft) without de-rating
De-rating factor for use at altitudes greater than 1000m
above sea level (IEC 62040-3)
0.95 @ 1500m / 4850ft asl
0.91 @ 2000m / 6600ft asl
0.86 @ 2500m / 8250ft asl
0.82 @ 3000m / 9900ft asl
Relative Air-humidity
Max. 95% (non-condensing)
Accessibility
Totally front accessibility for service and maintenance
(no need for side, top or rear access)
Positioning
Min. 200mm rear space (required for fan)
Input and Output Power Cabling
From the bottom on the front
Efficiency AC-AC up to (pf = 1.0)
(depending on Module power)
%
Load: 100% 75% 50% 25%
Efficiency: 94.5% 94.5% 94% 93%
Efficiency Non-linear Load (EN 62040-1-1:2003)
Typically up to 1% lower of above values
Eco-Mode efficiency at 100% load
%
98%
Heat Dissipation with 100% Non-linear Load per Module
(EN 62040-1-1)
W
1532
2043
2553
Heat Dissipation with 100% Non-linear Load per Module
(EN 62040-1-1)
BTU
5227
6969
8712
Airflow (25° - 30°C) with Non-linear Load per Module (EN
62040-1-1:2003)
m
3
/h
380
380
380