7: Options
7.2.6 SNMP/ CS141 slots – SLOT 1/ SLOT 2
Simple Network Management Protocol (SNMP) is a world-wide, standardised communication protocol that can be used to
monitor any network-connected device via a simple control language and display the results in an application running
within a standard web browser.
The customer interface board contains two SNMP/CS141 slots; one is designed to house a Modem/Ethernet SNMP
adapter card and the other a Modem/GSM adapter. SNMP connectivity can also be implemented using an external SNMP
adapter connected to the UPS RS232 output (JD11), as shown in Figure 7.5.
An SNMP/Ethernet adapter contains an RJ-45 connector which allows it to be connected to the network using a standard
CAT-5 network cable. Once connected, the UPS-Management software agent, which is already installed in the SNMP
adapter, then monitors the UPS operation and outputs its data in SNMP format to the connected network. In a multi-
module UPS system the SNMP interface can communicate ‘system-wide’ data or data for an individual UPS module.
The SNMP adaptor requires a PC with terminal connections, and for normal operation at least one Ethernet connection.
The SNMP card enables event/alarm emails, server shutdown (with optional licenses) and other tasks and can also be
integrated with BMS software over a local area network (LAN) for SNMP or Modbus information over IP. An optional card
is available to enable Modbus communications over RS485.
Figure 7.5 SNMP Internal and external SNMP adapters
SNMP MONITOR
ETHERNET
External SNMP Adapter
Internal SNMP Card
Slot 2
JD11