KNIGHT D-SERIES SERVO HOIST OPERATION MANUAL
SECTION 5
SOFTWARE
50
d. Drive Parameter verification and installation is required if you have updated the PLC or
replaced the Drive.
i. From the ‘Setup’ pulldown menu of the Yaskawa website page, select the
“Drive Parameters” option. (Refer to Figure 5-22)
Figure 5-22
ii. The User Drive Parameters will initially show a “Not Verified” result. Click on the
“Verify” to check the loaded ‘User Parameters’ parameters. The result will show as
“Verified” or “MISMATCH(Pn###)”. Any mismatch result means the User
Parameters must be written from the PLC to the Drive.
NOTE: Pn825 will occasionally show up as a mismatch drive parameter,
this should be disregarded.
iii. Make sure to use the “Write” command under ‘User Parameters’ column and
NOT
the one under the ‘Factory Default Parameters’ column. (Refer to Figure 5-23)
Figure 5-23