85
motor
At this time, computer software shows:
Notice: The positive and negative limits are default to normally closed point. Otherwise, the Panel will alarm
and display P.L (positive limit) and N.L (No limit). Only when the alarm is eliminated, the origin control mode
can be normally used.
Computer monitoring status is
:
2. Set parameters for homing.