Login the System - Section 2
You should also verify that the Communication Port and Address
DIP Switch are correct in the Configure Controller (MORE) win-
dow. The Communication Port must be the same as the port
selected in Workstation and the controller Address setting (from
1 to 16) must be the same as the physical address set by the
controller’s DIP switch setting.
Defining Controllers - Section 3
The KT-200 controllers are polled and identified by their individual
addresses configured by the on-board dipswitches. All readers
and zone inputs are connected to the controllers, as well as the
door strikes, output relays, and auxiliary outputs.
Programming Relays - Section 3
If extra relays are required, up to 14 more may be added (for a total
of 16) by adding REB-8 relay expansion boards.
Note: The REB-8 relay expansion board may be used only with the
KT-200.
Monitoring Inputs - Section 3
KT-200
WinPass can monitor 16 inputs per KT-200. Typically, 4 inputs
per KT-200 are reserved for the doors (a door contact, T.REX
request-to-exit detector for door 1 and, a door contact, T.REX
request-to-exit detector for door 2). The following diagram shows
how inputs are connected to a KT-200.
Programming Outputs - Section 3
KT-200
In addition to having two form C relays on each KT-200, four open-
collector auxiliary outputs have also been provided. These out-
puts are typically used to activate the reader’s LED on an access
granted/ and the piezo alarm buzzer on a T.REX request-to-exit
detector door alarm (please refer to the output definition in
section 5).
Controller Definition - Section 5
Input Connection
Configure one or two REB-8 relay expansion boards with the KT-
200 controller.
Door Definition - Section 5
Door address
COM2:01:01
The door address is a physical address consisting of the serial
port, the physical address of the controller (Dip switch of the KT-
200), and the physical address of the door (1 or 2). The door
address cannot be modified unless the controller serial port
setting is modified at which time the door address is automatically
changed by the system.
Door Contact Input
Input 1 is reserved for door 1 and Input 9 for door 2 by default for
the KT-200.
REX Input
Input 2 and Input 10 are reserved for REX on door 1 and REX on
door 2 for the KT-200.
Input Definition - Section 5
Input Address
COM2:01:01
The input address is a physical address consisting of the serial
port, the physical address of the controller (Dip switch for the KT-
200), and the physical address of the input (1 to 16).
Output Definition - Section 5
Output Address
COM2:01:01
The output address is a physical address consisting of the serial
port, the physical address of the controller (Dip switch for the KT-
200), and the physical address of the input (1 to 4).
Relay Definition - Section 5
Relay Address
COM2:01:01
The relay address is a physical address consisting of the serial
port, the physical address of the controller (Dip switch on the KT-
200), and the physical address of the relay (1 to 16).
Workstation Configuration - Section 5
Port Settings
Enter the value according to the DIP switch settings on the KT-
200 door controllers. The default value is 9600 baud.