Introduction
The KT-PC4108 module is a zone input module that adds up to 8 fully
programmable zones to the KT-300 controller.
1. Specifications
• Connects to the controller via 4-wire Combus
• Current draw: 30 mA (from Combus)
• Supports single end-of-line and no end-of-line (5600 ohm resistors)
zone loops.
• AUX+ output: 12VDC, 250mA max. (drawn from Combus)
• Tamper contact input
2. Installing the KT-PC4108
2.1
Unpacking
The KT-PC4108 package includes the following parts:
• One KT-PC4108 circuit board
• 16 end-of-line resistors (5600 ohm)
• Four (4) plastic standoffs
2.2
Mounting
The KT-PC4108 module should be located inside a compatible cabi-
net (Kantech part no. KT-4051CAB), mounted in a dry, secure loca-
tion. Preferably, it should be placed at a convenient distance from the
connected devices.
Perform the following steps to mount the unit:
1.
Press the four (4) plastic standoffs through the mounting holes
on the back of the cabinet.
2.
Secure the cabinet to the wall in the desired location. Use
appropriate wall anchors when securing the cabinet to drywall,
plaster, concrete, brick or any other surfaces.
3.
Press the circuit board into the four (4) plastic standoffs to
secure the unit to the cabinet.
Once the unit is mounted, wiring may be started.
2.3
Installation and Wiring
Before beginning to wire the unit, ensure that all power (AC trans-
former and battery) is disconnected from the controller.
KT
KT
KT
KT
KT-PC4108 - 8-Zone Input Expansion Module
-PC4108 - 8-Zone Input Expansion Module
-PC4108 - 8-Zone Input Expansion Module
-PC4108 - 8-Zone Input Expansion Module
-PC4108 - 8-Zone Input Expansion Module
Perform the following steps to complete wiring:
1.
Connect the four Combus wires to the KT-PC4108. Connect
the red, black, yellow and green Combus wires to the RED,
BLK, YEL and GRN terminals, respectively.
2.
Complete all zone wiring to the zone input terminals (Z1-Z8).
See the EntraPass or WinPass manual for details on zone wiring
configurations.
3.
Connect the external tamper switch, if used.
Consult the wiring diagram above for further information.
2.4
Applying Power
After all wiring is completed, apply power to the controller. Connect
the battery leads to the battery, then connect the AC transformer.
Note: Do not connect the power until all wiring is complete.
3. Assigning the Module
Once all wiring is complete, the module must be assigned to the
system. To assign the module, perform the following:
Once all wiring is complete, the module must be assigned to the
system. To assign the module, perform the following steps:
1.
Establish communication between the PC and the controller,
2.
Remove the tamper switch wire,
3.
A serial number should be displayed on the screen. In the same
window where the serial number is located, you should see the
type of module and on which controller it is connected,
4.
From the software, select the functionality of the module and
enter the serial number in the appropriate field (see controller
definition -- assign modules for more details).
Note: Don’t forget to reconnect the tamper switch (or the wire, if
there is no tamper switch)