8 Diagnosis / error messages
72
8.3 Overview
Errors encountered are itemized in tabular form on the following pages. The response of the transmitter on error detection is described
therein.
The table lists all possible errors together with a description of their impact on the value of measurement variables, the properties of
current outputs and the alarm output.
Error no. /
Area
Text on the LCD display
Current output
Digital output
Pulse output
LCD display
Maskable error?
F099.042 /
Electronics
ADC overrange alarm.
Noise too high. Check applicati.
Call service.
High Alarm or Low
Alarm depends on the
“Curr.Out at Alarm”
parameter setting.
General Alarm, if the
digital output has
been configured as a
“Logic / Alarm Signal”.
0
0 %
No
F098.012 /
Electronics
FEB communication error.
EMC disturbance. Call Service.
0
0 %
No
F097.029 /
Electronics
Coil regulation error.
Check wiring of sensor coils.
Call service
0
0 %
No
F096.043 /
Electronics
SIL self check alarm.
Call service.
No change; current
value.
No change; current
value.
No
F095.036 /
Electronics
Coil isolation alarm.
Call service.
No change; current
value.
No change; current
value.
No
F094.022 /
Electronics
Safety Alarm Curr. Out 31 / 32
SIL function detects error. Call
Service.
No change; current
value.
No change; current
value.
No
F093.032 /
Electronics
Electrode short cuircit.
Check wiring of sensor
electrode. Call service.
0
0 %
No
F092.033 /
Electronics
Electrode open cuircit.
Check wiring of sensor
electrode. Call service.
0
0 %
No
F091.030 /
Electronics
Coil wiring error.
Check wiring of sensor coils.
Call service.
0
0 %
No
F090.035 /
Electronics
ADC RX210 com. error.
Call service.
0
0 %
No
F088.013 /
Electronics
FEB communication error.
EMC disturbance. Call Service.
0
0 %
No
F086.019 /
Electronics
Curr.Out 31 / 32 com error.
Defective Board. EMC
disturbance. Call Service.
No change; current
value.
No change; current
value.
No
F084.011 /
Electronics
NV data defect.
Data storage irreparable. Call
Service.
0
0 %
No
F082.014 /
Electronics
Incompatible Frontend Board.
Frontend not fit to Motherboard.
Call Service.
0
0 %
No
F081.026 /
Electronics
MB voltages outside range.
Defective Motherboard HW. Call
Service.
0
0 %
No
Содержание 406060
Страница 2: ......
Страница 98: ...13 Appendix 98 13 3 Declarations of conformity 13 3 1 JUMO flowTRANS MAG S10...
Страница 99: ...13 Appendix 99...
Страница 100: ...13 Appendix 100...
Страница 101: ...13 Appendix 101...
Страница 102: ...13 Appendix 102...
Страница 103: ...13 Appendix 103...
Страница 104: ...13 Appendix 104 13 3 2 JUMO flowTRANS MAG H10...
Страница 105: ...13 Appendix 105...
Страница 106: ...13 Appendix 106...
Страница 107: ...13 Appendix 107...
Страница 108: ...13 Appendix 108...
Страница 109: ...13 Appendix 109...
Страница 110: ...13 Appendix 110 13 3 3 JUMO flowTRANS MAG 10...
Страница 111: ...13 Appendix 111...
Страница 112: ...13 Appendix 112...
Страница 113: ...13 Appendix 113...
Страница 115: ......