JOHNSON CONTROLS
136
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
SECTION 6 – USER INTERFACE
TABLE 35 -
SIMPLICITY ELITE DATA MAP (CONT'D)
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
7D H - 7F
L
125 H -
127 L
NA
NA
NA
Holiday #9 (Same Format As Holiday #1)
80 H - 82 L
128 H -
130 L
NA
NA
NA
Holiday #10 (Same Format As Holiday #1)
83 H - 85 L
131 H -
133 L
NA
NA
NA
Holiday #11 (Same Format As Holiday #1)
86 H - 88 L
134 H -
136 L
NA
NA
NA
Holiday #12 (Same Format As Holiday #1)
89 H - 8B
L
137 H -
139 L
NA
NA
NA
Holiday #13 (Same Format As Holiday #1)
8C H - 8E
L
140 H -
142 L
NA
NA
NA
Holiday #14 (Same Format As Holiday #1)
8F H - 91 L
143 H -
145 L
NA
NA
NA
Holiday #15 (Same Format As Holiday #1)
92 H - 94 L
146 H -
148 L
NA
NA
NA
Holiday #16 (Same Format As Holiday #1)
95 H - 97 L
149 H -
151 L
NA
NA
NA
Holiday #17 (Same Format As Holiday #1)
98 H - 9A L
152 H -
154 L
NA
NA
NA
Holiday #18 (Same Format As Holiday #1)
9B H - 9D
L
155 H -
157 L
NA
NA
NA
Holiday #19 (Same Format As Holiday #1)
9E H - A0L
158 H -
160 L
NA
NA
NA
Holiday #20 (Same Format As Holiday #1)
A1 H
161 H
-
0
255
Supply Air Temperature (1/10 Degrees, High BYTE, 16 Bit
Value, 0 = -40 Degrees F)
A1 L
161 L
-
0
255
Supply Air Temperature (1/10 Degrees, Low BYTE, 16 Bit
Value, 0 = -40 Degrees F)
A2 H
162 H
-
0
255
Outside Air Temperature (1/10 Degrees, High BYTE, 16 Bit
Value, 0 = -40 Degrees F)
A2 L
162 L
-
0
255
Outside Air Temperature (1/10 Degrees, Low BYTE, 16 Bit
Value, 0 = -40 Degrees F)
A3 H
163 H
-
0
255
Return Air Temperature (1/10 Degrees, High BYTE, 16 Bit
Value, 0 = -40 Degrees F)
A3 L
163 L
-
0
255
Return Air Temperature (1/10 Degrees, Low BYTE, 16 Bit
Value, 0 = -40 Degrees F)
A4 H
164 H
-
0
255
Space Sensor Temperature (Room Air) (1/10 Degrees, High
BYTE, 16 Bit Value, 0 = -40 Degrees F)
A4 L
164 L
-
0
255
Space Sensor Temperature (Room Air) (1/10 Degrees, Low
Byte, 16 Bit Value, 0 = -40 Degrees F)
A5 L
165 L
3
0
5
Space Sensor Offset Range (Degrees)
A6 L
166 L
-
0
100
Return Air Humidity (%)
A7 L
167 L
-
0
100
Outside Air Humidity (%)
A8 H
168 H
-
0
255
Demand Ventilation (IAQ) Value (PPM Value, High BYTE)
A8 L
168 L
-
0
255
Demand Ventilation (IAQ) Value (PPM Value, Low BYTE)
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...