SECTION 5 – SEQUENCE OF OPERATION
Demand Ventilation
In this mode the Simplicity Elite control monitors the
CO
2
level in the conditioned space. The Simplicity
Elite control modulates the outdoor air damper beyond
the
“ECONOMIZER MINIMUM POSITION”
in order
to keep the CO
2
level within plus or minus 100 PPM of
the
“IAQ SETPOINT”.
In order to use this feature a CO
2
sensor must be in-
stalled in the conditioned space and connected to
“DV+”
and the
“DV-“
terminals of the P20 connector.
The following parameters must be programmed to en-
able Demand Ventilation:
•
“ECONOMIZER INSTALLED”
– must be en-
abled using Parameter 32 under the PROGRAM
key on the Simplicity Elite control board or under
the ECONOMIZER/EXHAUST tab in the Sim-
plicity PC software package.
•
“ECONOMIZER MINIMUM POSITION”
– must
be programmed using Parameter 35 under the
PROGRAM key on the Simplicity Elite control
board or under the ECONOMIZER/EXHAUST
tab in the Simplicity PC software package.
•
“DEMAND VENTILATION (IAQ) ENABLED”
– must be enabled using Parameter 40 under the
PROGRAM key of the Simplicity Elite control
board or under the COMFORT / DEMAND VEN-
TILATION tab in the Simplicity PC software
package.
•
“IAQ SENSOR RANGE”
- must be programmed
using Parameter 41 under the PROGRAM key
on the Simplicity Elite control board or under the
COMFORT / DEMAND VENTILATION tab in
the Simplicity PC software package.
•
“IAQ SETPOINT”
- must be programmed using
Parameter 42 under the PROGRAM key on the
Simplicity Elite control board or under the COM-
FORT / DEMAND VENTILATION tab in the
Simplicity PC software package.
•
“MAXIMUM IAQ ECONOMIZER POSITION”
–
must be programmed under the COMFORT / DE-
MAND VENTILATION tab in the Simplicity PC
software package.
Definitions
The following definitions apply to Demand Ventila-
tion:
•
“IAQ SENSOR RANGE”
–This establishes the
span the Simplicity Elite control uses in PPM.
0 PPM would be equal to a 0 volts input to the
Simplicity Elite control,
“IAQ SENSOR RANGE”
would be equal to 10 volts input to the Simplicity
Elite control. The
“IAQ SENSOR RANGE”
must
match the PPM range of the sensor installed in the
conditioned space.
•
“IAQ SETPOINT”
– This is the conditioned space
CO
2
level the Simplicity Elite control is trying to
maintain.
•
“MAXIMUM IAQ ECONOMIZER POSITION”
– This is the maximum damper position the Sim-
plicity Elite control will allow the damper to open
while in a Demand Ventilation mode no matter
how great a differential is between the conditioned
space CO
2
level and the
“IAQ SETPOINT”.
Sequence of Operation
The damper will open to the programmed
“ECONO-
MIZER MINIMUM POSITION”
whenever the follow-
ing conditions are met:
•
The unit is in the occupied mode.
•
There must be a 24-volt output from the Simplic-
ity Elite control to the supply fan control circuit.
The output is contained at the “FAN” terminal
of connector P13 on the Simplicity Elite control
board.
•
When the economizer becomes active the position
of the dampers are controlled by the Economizer
PI logic which could move the dampers beyond
the
“ECONOMIZER MINIMUM POSITION”
;
however, the Economizer PI logic can never close
the dampers less than the
“ECONOMIZER MINI-
MUM POSITION”.
If the above criteria are met, the Simplicity Elite con-
trol will then monitor the CO
2
level in the conditioned
space and vary the position of the outdoor air damper
between the
“ECONOMIZER MINIMUM POSITION”
and the
“MAXIMUM IAQ ECONOMIZER POSI-
TION”
based on the following:
•
The Simplicity Elite control will try to maintain
the CO
2
level in the conditioned space to plus or
minus 100 PPM of the
“IAQ SETPOINT”.
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...