JOHNSON CONTROLS
137
SECTION 6 – USER INTERFACE
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
6
TABLE 35 -
SIMPLICITY ELITE DATA MAP (CONT'D)
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
A9 H
169 H
-
0
255
Building Pressure Value (0.001" WC, High BYTE, 0 =
-0.250" WC, Max = 0.250" WC)
A9 L
169 L
-
0
255
Building Pressure Value (0.001" WC, Low BYTE, 0 =
-0.250" WC, Max = 0.250" WC)
AA H
170 H
-
0
255
Duct Pressure Value (0.01" WC, High BYTE, 0 = 0.00" WC,
Max = 5.00" WC)
AA L
170 L
-
0
255
Duct Pressure Value (0.01" WC, Low BYTE, 0 = 0.00" WC,
Max = 5.00" WC)
AB H
171 H
0
0
200
Remote Control Input Value (0.05 VDC Counts For Cooling
Sat Setpoint Scaling)
AB L
171 L
40
0
200
Demand Ventilation Setpoint (25 PPM Increments,
Maximum 5000 PPM)
AC L
172 L
80
0
200
Air Quality (DV) Sensor Range (25 PPM Increments,
Maximum 5000 PPM)
AD L
173 L
60
0
240
Unoccupied Override Time Period (Minutes)
AE H
174 H
45
0
100
Outdoor Air Temperature Cooling Lockout Temperature
(Degrees F, 0 = Disabled)
AE L
174 L
75
0
100
Outdoor Air Temperature Heating Lockout Temperature
(Degrees F, 0 = Disabled)
AF H
175 H
50
40
65
Sat Cooling Limit Setpoint (Degrees F)
AF L
175 L
135
100
180
Sat Heating Limit Setpoint (Degrees F)
B0 H
176 H
120
80
180
Hydronic Heating Stage #1 Supply Air Setpoint (Degrees F)
B0 L
176 L
150
80
180
Hydronic Heating Stage #2 Supply Air Setpoint (Degrees F)
B1 H
177 H
80
60
85
Comfort Ventilation Upper Setpoint (Degrees F)
B1 L
177 L
70
60
85
Comfort Ventilation Lower Setpoint (Degrees F)
B2 H
178 H
60
40
70
VAV Cooling Supply Air Temperature: Upper Setpoint
(Degrees F)
B2 L
178 L
55
40
70
VAV Cooling Supply Air Temperature: Lower Setpoint
(Degrees F)
B3 H
179 H
72
40
85
VAV Cooling Supply Air Temperature: Reset Setpoint
(Degrees F)
B3 L
179 L
68
40
85
VAV Occupied Heating Setpoint (Degrees F)
B4 H
180 H
70
50
85
Morning Warm Up And VAV Heating: Return Air
Temperature Setpoint (Degrees F)
B5 H
181 H
60
0
200
Duct Pressure Setpoint (0.025" Wc Increments,
Default = 1.500" WC « 60)
B5 L
181 L
180
0
200
Duct Pressure Shutdown Setpoint (0.025" Wc Increments,
Default = 4.500" WC « 180)
B6 H
182 H
70
0
100
Building Pressure Setpoint (0.005" WC Increments,
0 = -0.250" WC, Default = 0.100" WC « 70)
B7 H
183 H
55
40
65
Economizer First Stage (Upper) Setpoint (Degrees F)
B7 L
183 L
50
40
65
Economizer Second Stage (Lower) Setpoint (Degrees F)
B8 H
184 H
20
0
100
Economizer Minimum Position (Percent)
B9 H
185 H
27
10
50
Economizer Outside Air Enthalpy Setpoint (BTU Per Pound)
B9 L
185 L
27
10
50
Economizer Return Air Enthalpy Setpoint (BTU Per Pound)
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...