SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS
TABLE 36 –
DEFINITIONS (CONT'D)
MENU ITEM
DEFINITION
ECONOMIZER OUTSIDE AIR TEMP ENABLE
SETPOINT
This is the outdoor temperature which determines when to switch into
and out of economizer operation
ECONOMIZER SECOND STAGE SETPOINT
On a Constant Volume unit the Unit Controller will try and maintain the
supply air temperature at this setpoint in the economizer mode with a
second stage cooling call
ERV INSTALLED
This parameter must be turned On if an Energy Recovery Ventilator is
installed. This feature is currently not available on these units
ERV UNOCCUPIED FAN ENABLE
This parameter allows the exhaust fan to operate anytime the
supply fan is on. This feature is required when an Energy Recovery
Ventilator is installed. This feature is currently not used on these units.
EXHAUST DAMPER POSITION FOR EXHAUST
TO TURN OFF
When MODULATING DAMPER exhaust is being used this is the
position of the exhaust damper to turn off the exhaust fan
EXHAUST DAMPER POSITION FOR EXHAUST
TO TURN ON
When MODULATING DAMPER exhaust is being used this is the
position of the exhaust damper to turn on the exhaust fan
EXHAUST FAN OUTPUT
This gives the status of the binary output from the Unit Controller to
the exhaust fan, OFF or ON
EXHAUST DAMPER / VFD OUTPUT STATUS
This gives the status of the analog Unit Controller output to the
exhaust damper or exhaust fan VFD in %
EXHAUST VFD INSTALLED
This parameter identifies to the Unit Controller that an exhaust fan
VFD is installed. The parameter must be turned ON to enable this
feature
FAN (G) THERMOSTAT INPUT
This gives the status of the binary input to the G terminal of the Unit
Controller, OFF or ON
FAN ASD TIMER
This is the status of the supply fan off delay in seconds
FAN OFF DELAY TIMER FOR COOL
This gives the status of the cooling time off delay in seconds
FAN OFF DELAY TIMER FOR HEAT
This gives the status of the cooling time off delay in seconds
FAN ON DELAY TIMER FOR COOL
This gives the status of the cooling time on delay in seconds
FAN ON DELAY TIMER FOR HEAT
This gives the status of the cooling time on delay in seconds
FREEZE THERMOSTAT SWITCH
This is the binary input from the hydronic heat freeze stat to the Unit
Controller. OFF = faulted, ON = Normal Operation
GAS VALVE #1
This is the status of the binary input from the gas valve for heat
section 1 to the Unit Controller OFF / ON
GAS VALVE #2
This is the status of the binary input from the gas valve for heat
section 2 to the Unit Controller OFF / ON
GAS VALVE #3
This is the status of the binary input from the gas valve for heat
section 3 to the Unit Controller OFF / ON
HEAT 1 (W1)
This is the status of the binary input to terminal W1 - first stage heating
HEAT 1 ASCD TIMER
This gives the actual time of the off cycle timer for heat section 1 in
seconds.
HEAT 1 MIN RUN TIMER
This gives the actual time of the minimum run time timer for heat
section 1 in seconds
HEAT 2 (W2)
This is the status of the binary input to terminal W2 - second stage
heating
HEAT 2 ASCD TIMER
This gives the actual time of the off cycle timer for heat section 2 in
seconds.
HEAT 2 MIN RUN TIMER
This gives the actual time of the minimum run time timer for heat
section 2 in seconds
HEAT 3 (W3)
This is the status of the binary input to terminal W3 - third stage
heating
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...