JOHNSON CONTROLS
130
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
SECTION 6 – USER INTERFACE
TABLE 35 -
SIMPLICITY ELITE DATA MAP
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
00 H
0 H
NA
20
NA
NA
Device ID = 20 For Elite
00 L
0 L
NA
-
0
255
Device Software Revision
01 H
1 H
NA
54
-
-
Option Byte #1
0
Bits 1 And 0 = 0,0 Respectively There Are 0 Stages Of
Heat; 0,1 = 1 Stage; 1,0 = 2 Stages; 1,1 = 3 Stages
1
2
1 = Heating Mode Enabled For Operation
3
Heat 1 = Turn Off Continuous Fan When Starting
4
1 = Cooling Mode Enabled For Operation
5
1 = Economizer Loading Active
6
1 = Space Sensor Fault Override Enabled
7
NA
01 L
1 L
NA
NA
NA
NA
Active Alarm
02 H
2 H
NA
30
0
30
Fan On Delay For Heat (Seconds)
02 L
2 L
NA
60
0
255
Fan Off Delay For Heat (Seconds)
03 H
3 H
NA
0
0
30
Fan On Delay For Cool (Seconds)
03 L
3 L
NA
30
0
255
Fan Off Delay For Cool (Seconds)
04 L
4 L
NA
3
1
10
Minimum Run Time For Compressors (Minutes)
05 H
5 H
NA
0
0
255
Heating #1 Accumulated Run Time (Hours, High BYTE)
05 L
5 L
NA
0
0
255
Heating #1 Accumulated Run Time (Hours, Low BYTE)
06 H
6 H
NA
0
0
255
Heating #2 Accumulated Run Time (Hours, High BYTE)
06 L
6 L
NA
0
0
255
Heating #2 Accumulated Run Time (Hours, Low BYTE)
07 H
7 H
NA
0
0
255
Heating #3 Accumulated Run Time (Hours, High BYTE)
07 L
7 L
NA
0
0
255
Heating #3 Accumulated Run Time (Hours, Low BYTE)
08 H - 14 L 8 H - 20 L
NA
Registers 8 - 20 Store The Unit Name. When Written, All 13
Registers (At 2 Bytes Per Register) Should Be Written. The
Format Is Ascii. Character #1 Is In 8 H. Character #2 Is In 8
L. Character #3 Is In 9 H, And So On.
15 H
21 H
NA
-
-
-
Input Status Byte #1
0
1 = Y1 On (Cooling 1st Stage)
1
1 = Y2 On (Cooling 2nd Stage)
2
1 = Y3 On (Cooling 3rd Stage)
3
1 = Y4 On (Cooling 4th Stage)
4
1 = W1 On (Heating 1st Stage)
Writing to any register not in this list may
cause erratic operation.
This product is not designed to accept
continuous writes to data stored in long
term memory. It is recommended that no
stored value be changed more often than
an average of once per hour. Changing
data more often risks damaging the ability
of the control to store new data for the full
life of the product.
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...