JOHNSON CONTROLS
139
SECTION 6 – USER INTERFACE
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
6
TABLE 35 -
SIMPLICITY ELITE DATA MAP (CONT'D)
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
CA L
202 L
0
-
-
Compressor #4 Minimum Run Timer Low BYTE (Seconds,
Counts Down)
CB H
203 H
-
-
-
Fan ASCD Timer High BYTE (Always Zero)
CB L
203 L
-
-
-
Fan ASCD Timer Low BYTE. (Seconds, Counts Down)
CC H
204 H
0
-
-
Fan Minimum Run Timer (Seconds, Counts Down)
CD H
205 H
0
-
-
Fan On Delay Timer For Heat (Seconds, Count Down)
CD L
205 L
0
-
-
Fan Off Delay Timer For Heat (Seconds, Count Down)
CE H
206 H
0
-
-
Fan On Delay Timer For Cool (Seconds, Count Down)
CE L
206 L
0
-
-
Fan Off Delay Timer For Cool (Seconds, Count Down)
CF H
207 H
0
0
255
Accumulated Unoccupied Override Time (Hours, High
BYTE)
CF L
207 L
0
0
255
Accumulated Unoccupied Override Time (Hours, Low
BYTE)
D4 H
212 H
-
0
100
Supply Fan VFD Output Status, 0-100% (2 – 10VDC)
D4 L
212 L
-
0
100
Exhaust Damper Output Status, 0-100% (2 – 10VDC)
D5 H
213 H
-
0
100
Hot Water Valve Output Status, 0-100% (2 – 10VDC)
D5 L
213 L
-
0
100
Hot Gas Reheat Valve Output Status, 0-100% (2 – 10VDC)
D6 H
214 H
-
0
100
Economizer Damper Output Status, 0-100% (2 – 10VDC)
D7 H
215 H
NA
0
-
-
Option Byte #6
0
1 = Comfort Ventilation For Cooling Enabled
1
1 = Comfort Ventilation For Heating Enabled
2
1 = Temperature / Humidity Control Enabled
3
1 = Hot Gas Reheat Alternate Operation Enabled
4
1 = Network Occupied Flag: OCC Is On
5
NA
6
1 = Differential Enthalpy Mode Enabled
7
NA
D7L
215 L
NA
0
-
-
Option BYTE #7
0
1 = ERV Enabled
1
1 = ERV Unoccupied Fan Enabled
2-7
NA
D8 H
216 H
s
0
100
Hot Gas Reheat Humidity Setpoint (Percent Humidity)
D8 L
216 L
50
20
80
Temperature / Humidity Setpoint (Percent Humidity)
D9 H
217 H
3
0
5
Maximum Temperature / Humidity Offset (Degrees F)
D9 L
217 L
5
1
10
Temperature / Humidity Value That = 1° F Of Offset
(Percent Humidity)
DB H
219 H
72
45
99
Operating Cooling Setpoint (Degrees F) [CV]
DB L
219 L
68
45
99
Operating Heating Setpoint (Degrees F) [CASCD]
DC H
220 H
-
10
50
Outside Air Enthalpy (BTUS Per Pound)
DC L
220 L
-
10
50
Return Air Enthalpy (BTUS Per Pound)
DE L
222 L
50
0
100
Maximum Demand Ventilation Economizer Position
(Percent Open)
DF H
223 H
-
0
10
Space Sensor Offset (0 = -5° F, 10 = +5° F)
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...