SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
7
TABLE 36 –
DEFINITIONS (CONT'D)
MENU ITEM
DEFINITION
HEAT 3 ASCD TIMER
This gives the actual time of the off cycle timer for heat section 3 in
seconds.
HEAT 3 MIN RUN TIMER
This gives the actual time of the minimum run time timer for heat
section 3 in seconds
HEAT FAN OFF DELAY
In the intermittent fan mode this is the time delay between the time the
heat call is terminated and the shut down of the supply fan
HEAT FAN ON DELAY
In the intermittent fan mode this is the time delay between the time the
heating operation is verified and the start of supply fan operation
HEATING MODE ENABLED FOR OPERATION
This parameter must be turned on to allow heating operation
HEATING NUMBER #1 ACCUMULATED RUNTIME This is the number of hours that Heating System 1 has been operative
HEATING NUMBER #2 ACCUMULATED RUNTIME This is the number of hours that Heating System 2 has been operative
HEATING NUMBER #3 ACCUMULATED RUNTIME
This is the number of hours that Heating System 3 has been
operative
HEATING OUTPUT #1 (H1)
This is the status of the binary output from the Unit Controller to heat
section # 1, OFF/ON
HEATING OUTPUT #2 (H2)
This is the status of the binary output from the Unit Controller to heat
section # 2, OFF/ON
HEATING OUTPUT #3 (H3)
This is the status of the binary output from the Unit Controller to heat
section # 3, OFF/ON
HOT GAS PRESENT ON COMPRESSOR # 1
This parameter must be turned on when Hot Gas Bypass is installed
HOT GAS REHEAT
This parameter would be turned ON to enable HOT GAS REHEAT.
This feature is not available on these units
HOT WATER VALVE OUTPUT STATUS
This gives the status of the analog Unit Controller output to the
hydronic valve in %
HOT WATER VALVE OUTPUT STATUS
(REVERSE ACTING)
This gives the status of the analog Unit Controller output to the
hydronic valve in % when the unit is programmed for a reverse acting
valve
HOUR
This parameter is used to enter the hour of the current time based on
a 24 hour schedule, 13 would be 1 PM
HSP1
This is the status of the binary input from the high pressure switch for
compressor system 1 to the Unit Controller. ON - okay, OFF - faulted.
HSP2
This is the status of the binary input from the high pressure switch for
compressor system 2 to the Unit Controller. ON - okay, OFF - faulted.
HSP3
This is the status of the binary input from the high pressure switch for
compressor system 3 to the Unit Controller. ON - okay, OFF - faulted.
HSP4
This is the status of the binary input from the high pressure switch for
compressor system 4 to the Unit Controller. ON - okay, OFF - faulted.
HYDRONIC HEAT ACTUATOR VALVE REVERSE
ACTING
This parameter reverses the action of the hydronic valve. When the
parameter is turned ON a 2 volt input to the valve is full open and a 10
volt input to the valve is full closed
HYDRONIC HEATING ENABLED
This parameter must be turned ON to enable hydronic heating
operation
HYDRONIC HEATING STAGE #1 SUPPLY AIR
SETPOINT
This parameter establishes the setpoint for Constant Volume hydronic
heating operation during first stage operation
HYDRONIC HEATING STAGE #2 SUPPLY AIR
SETPOINT
This parameter establishes the setpoint for Constant Volume hydronic
heating operation during second stage operation and also the control
setpoint for VAV hydronic heating operation
IAQ SENSOR RANGE
This parameter identifies to the Unit Controller the range of the CO
2
sensor in PPM
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...