JOHNSON CONTROLS
46
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
SECTION 2 – INSTALLATION
TABLE 17 -
THREE PHASE POWER SUPPLY CONDUCTOR SIZE RANGE
050-061 MODELS
SUPPLY
VOLTAGE
SINGLE POINT
TB
SINGLE POINT
DISCONNECT
DUAL POINT TB
TB 1
TB 2
208V
(2*) 250 kcmil-500 kcmil
(2*) 2 AWG-500 kcmil
6 AWG-400 kcmil
6 AWG-350 kcmil
230V
(2*) 250 kcmil-500 kcmil
(2*) 2 AWG-500 kcmil
6 AWG-400 kcmil
6 AWG-350 kcmil
380V-60
6 AWG-400 kcmil
6 AWG-350 kcmil
14 AWG-2/0
14 AWG-2/0
460V
6 AWG-400 kcmil
6 AWG-350 kcmil
14 AWG-2/0
14 AWG-2/0
575V
6 AWG-400 kcmil
6 AWG-350 kcmil
14 AWG-2/0
14 AWG-2/0
CONTROLS
TRANSDUCER PNEUMATIC TUBING
Static Pressure Control Plastic Tubing
(Pneumatic Tubing)
Duct static transducers (all VAV units) and any unit
with an optional building pressure control transducer,
require pneumatic tubing to be field supplied and in-
stalled. Both the duct static transducer (VAV only) and
optional building pressure transducer are mounted be-
hind the right hand damper door. All wiring from the
transducers is factory installed.
Duct Static Transducer
Plastic tubing (3/16" ID) must be run from the high
pressure tap of the transducer to a static pressure tap
(field supplied) in the supply duct, located at a point
where constant pressure is desired. This is normally
2/3rds of the way down the duct, before the first take
off.
Building Pressure Transducer
Plastic tubing (3/16" ID) must be run from the high
pressure tap of the building static pressure transduc-
er to a static pressure tap (field supplied), located in
the conditioned space. The tap should be placed in a
location where over pressurization will cause a prob-
lem, for example, in the lobby area where excessive
pressure will cause the doors to remain open. The tap
should never be placed above the ceiling.
Static Pressure Probe Installation
On units with duct static transducers (VAV units) and
any unit with an optional building pressure, a factory
supplied Static Pressure Probe must be field installed
at the top of the rear corner post on the unit - see
.
The factory supplied atmospheric pressure probe and
associated mounting hardware are shipped inside the
unit control panel. The hardware consists of a mount-
ing bracket and a short section of pneumatic tubing.
The pneumatic tubing must be field installed from a
factory pressure tap (next to the mounting location for
the static pressure probe) to the atmospheric pressure
probe.
If the unit is equipped with both a building pressure
transducer and a duct static transducer, a “tee” will
be factory installed, and both the Duct Static Pressure
Transducer and building pressure will be connected to
the “tee” - both building static pressure transducer and
duct static transducer will use the same factory sup-
plied atmospheric pressure probe.
The “low” side connection of the
duct static or building pressure transduc-
ers are shipped with the pneumatic tubing
factory installed and routed, to the exter-
nal factory pressure tap.
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...