SECTION 5 – SEQUENCE OF OPERATION
Heating Operation – Occupied or Unoccupied
The Simplicity Control will stage ON the heat as fol-
lows:
•
When the space temperature is 1.5° F to 1.9° F
below the
“CV OCCUPIED HEATING”
or
“CV
UNOCCUPIED HEATING SETPOINT”
the con-
trol energizes the first stage of heat.
•
When the space temperature is 2.0° F to 2.4° F
below the
“CV OCCUPIED HEATING”
or
“CV
UNOCCUPIED HEATING SETPOINT”
the con-
trol energizes the second stage of heat.
•
When the space temperature is 2.5° F or more
below the
“CV OCCUPIED HEATING”
or
“CV
UNOCCUPIED HEATING SETPOINT”
the con-
trol energizes the third stage of heat.
The Simplicity Control will stage off the heat as fol-
lows:
•
When the space temperature is 2.4° F below the
“CV OCCUPIED HEATING”
or
“CV UNOCCU-
PIED HEATING SETPOINT”
the third stage of
heating will turn off.
•
When the space temperature is 1.9° F below the
“CV OCCUPIED HEATING”
or
“CV UNOCCU-
PIED HEATING SETPOINT”
the second stage of
heat will turn off.
•
When the space temperature is 0.1° F above the
“CV OCCUPIED HEATING”
or
“CV UNOCCU-
PIED HEATING SETPOINT”
the first stage of
heating will turn off.
The Simplicity Control has the following heating tim-
ing functions:
•
A minimum off time of 2 minutes.
•
A minimum ON time of 3 minutes.
•
There is a 30 second time delay between stages.
Stand Alone
The following System Parameters must be programmed
through the Simplicity Control:
•
“CV OCCUPIED COOLING SETPOINT”
– us-
ing Parameter 10 under the PROGRAM key on
the Simplicity control board or under the COOL-
ING SETUP tab in the Simplicity PC software
package.
•
“CV OCCUPIED HEATING SETPOINT”
– using
Parameter 11 under the PROGRAM key on the
Simplicity control board or under the HEATING
SETUP tab in the Simplicity PC software pack-
age.
•
“CV UNOCCUPIED COOLING SETPOINT”
–
using Parameter 12 under the PROGRAM key on
the Simplicity control board or under the COOL-
ING SETUP tab in the Simplicity PC software
package.
•
“CV UNOCCUPIED HEATING SETPOINT”
–
using Parameter 13 under the PROGRAM key on
the Simplicity control board or under the HEAT-
ING SETUP tab in the Simplicity PC software
package.
•
“SPACE SENSOR FAULT OVERIDE ENABLED”
must be turned ON – using Parameter 8 under the
PROGRAM key on the Simplicity control board
or under the SYSTEM OPTIONS tab in the Sim-
plicity PC software package.
Cooling Operation – Occupied or Unoccupied
The Simplicity Control will stage ON the cooling at
cooling start up as follows:
•
I
f the return air temperature is between 1.5° F and
1.9° F above the
“CV OCCUPIED COOLING
SETPOINT”
or
“CV UNOCCUPIED COOL-
ING SETPOINT”
the control will turn on the first
compressor from System 1 and turn on a 5 minute
timer.
•
If after 5 minutes the return air temperature is be-
tween 1.5° F and 1.9° F above the
“CV OCCU-
PIED COOLING SETPOINT”
or
“CV UNOC-
CUPIED COOLING SETPOINT”
the control will
bring on the second compressor of System 1 and
start a 5-minute timer.
OR
•
If the return air temperature is greater than 2.0° F
or more above the
“CV OCCUPIED COOLING
SETPOINT”
or
“CV UNOCCUPIED COOLING
SETPOINT”
the control will bring on the first
compressor from System 1 and start a 3 minute
timer. After 30 seconds, the control will bring on
the second compressor from System 1.
The Simplicity Control will stage ON the cooling after
3 or 5 minutes as follows:
•
If after 3 or 5 minutes the return air temperature is
between 1.5° F and 1.9° F above the
“CV OCCU-
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...