JOHNSON CONTROLS
132
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
SECTION 6 – USER INTERFACE
TABLE 35 -
SIMPLICITY ELITE DATA MAP (CONT'D)
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
2
1 = Alarms / Change Button Pressed
3
1 = Address / Down Button Pressed
4
NA
5
NA
6
NA
7
NA
18 H
24 H
NA
-
-
-
Output Status BYTE #1
0
1 = Compressor #1 On
1
1 = Compressor #2 On
2
1 = Compressor #3 On
3
1 = Compressor #4 On
4
1 = Condenser Fan #1 On
5
1 = Condenser Fan #2 On
6
1 = Indoor Fan On
7
1 = Exhaust Fan On
18 L
24 L
NA
-
-
-
Output Status BYTE #2
0
1 = Stage 1 Heat On
1
1 = Stage 2 Heat On
2
1 = Stage 3 Heat On
3
NA
4
NA
5
NA
6
NA
7
NA
19 H
25 H
NA
-
-
-
Output Status Byte #3
0
1 = Compressors Off Because Free Cooling Is Available
1
1 = Compressors Off Because Of Low Ambient
2
1 = Compressors Off Because Supply Voltage Is Low
3
1 = Control Is In Comfort Ventilation Mode
4
1 = Disable Control Is Active
5
1 = Economizer Is Using Free Cooling
6
NA
7
NA
19 L
25 L
NA
-
-
-
Output Status BYTE #4
0
1 = Compressor #1 Off Because Of ASCD
1
1 = Compressor #2 Off Because Of ASCD
2
1 = Compressor #3 Off Because Of ASCD
3
1 = Compressor #4 Off Because Of ASCD
4
NA
5
NA
6
NA
7
NA
1A H
26 H
NA
12
-
-
Option BYTE #2
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...