SECTION 5 – SEQUENCE OF OPERATION
The following parameters must be programmed:
•
“COMFORT VENTILATION FOR COOLING
ENABLED”
- must be enabled under the COOL-
ING SETUP tab in the Simplicity PC software
package.
•
“COMFORT VENTILATION FOR HEATING
ENABLED”
- must be enabled under the HEAT-
ING SETUP tab in the Simplicity PC software
package.
•
“COMFORT VENTILATION UPPER
SETPOINT”
- must be programmed under the
COOLING SETUP or HEATING SETUP tab in
the Simplicity PC software package.
•
“COMFORT VENTILATION LOWER
SETPOINT”
- must be programmed under the
COOLING SETUP or HEATING SETUP tab in
the Simplicity PC software package.
Sequence of Operation
use the following definitions:
•
SAT COMFORT ZONE – the temperature be-
tween the
“COMFORT VENTILATION LOWER
SETPOINT”
minus 1.0° F and the
“COMFORT
VENTILATION UPPER SETPOINT”
plus 1.0° F.
•
OAT COMFORT ZONE - the temperature be-
tween the
“COMFORT VENTILATION LOWER
SETPOINT”
and the
“COMFORT VENTILA-
TION UPPER SETPOINT”.
•
OAT – Outdoor Air Temperature.
•
SAT – Supply Air Temperature.
•
ECON OPERATION – Economizer damper will
open to BRING SAT into the SAT COMFORT
ZONE.
Conditions of Operation
For Comfort Ventilation to function the following con-
ditions of operation must be met:
•
In order for compressor operation
“COMFORT
VENTILATION FOR COOLING ENABLED”
must be enabled.
•
In order for heat stages to operate
“COMFORT
VENTILATION FOR HEATING ENABLED”
must be enabled.
•
Economizer operation will occur with either, or
both,
“COMFORT VENTILATION FOR COOL-
ING ENABLED”
or
“COMFORT VENTILATION
FOR HEATING ENABLED”
enabled.
EXCESSIVE SAT (SUPPLY AIR TEMPERATURE)
CONTROL
This feature is only available on Constant Volume
units. On a Constant Volume unit, the compressors
and heat stages are control by the space temperature
only, either by thermostat or zone sensor. As long as
the room device is calling for cooling or heating the
compressors or heating section does not control the ac-
tual temperature of the supply air leaving the unit. The
enabling of this feature adds a means to prevent low or
high supply air temperatures from being delivered to
the conditioned space.
Cooling
The following System Parameters must be pro-
grammed:
•
“SUPPLY AIR TEMP LIMIT FOR COOLING
ENABLED”
- must be enabled using Parameter 14
under the PROGRAM key on the Simplicity con-
trol board or under the COOLING SETUP tab in
the Simplicity PC software package.
TABLE 32 -
HEAT STAGE ON WHEN SPACE INPUT SATISFIED
OAT VS OAT COMFORT ZONE SAT VS SAT COMFORT ZONE ECON OPERATION HEAT STAGE COMP STAGE
BELOW
ABOVE
OPEN
LEAVE ON*
-
BELOW
BELOW
-
LEAVE ON
-
BELOW
WITHIN
-
LEAVE ON
-
ABOVE
ABOVE
-
TURN OFF
TURN ON
ABOVE
BELOW
OPEN
TURN OFF
-
ABOVE
WITHIN
-
TURN OFF
-
WITHIN
ABOVE
OPEN
TURN OFF
-
WITHIN
BELOW
OPEN
TURN OFF
-
WITHIN
WITHIN
-
TURN OFF
-
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...