JOHNSON CONTROLS
138
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
SECTION 6 – USER INTERFACE
TABLE 35 -
SIMPLICITY ELITE DATA MAP (CONT'D)
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
BA H
186 H
55
40
80
Economizer Outside Air Temperature Enable Setpoint
(Degrees F)
BB H
187 H
4
0
23
Pre-Occupancy Purge Time (Hours)
BB L
187 L
0
0
59
Pre-Occupancy Purge Time (Minutes)
BC H
188 H
80
10
100
Exhaust Damper Position For Exhaust Fan To Turn On –
Modulating Only (Percent)
BC L
188 L
20
0
90
Exhaust Damper Position For Exhaust Fan To Turn Off –
Modulating Only (Percent)
BD H
189 H
60
10
100
Economizer Damper Position For Exhaust Fan To Turn On
– Non-Modulating Only (Percent)
BD L
189 L
20
0
90
Economizer Damper Position For Exhaust Fan To Turn Off
– Non-Modulating Only (Percent)
BE H
190 H
0
0
80
Supply Air Temperature Alarm Setpoint For Cooling
(Degrees F, 0 = Disabled)
BE L
190 L
0
0
120
Supply Air Temperature Alarm Setpoint For Heating
(Degrees F, 0 = Disabled)
BF H
191 H
5
0
25
Space Sensor Alarm Temperature (Degrees F, 0 =
Disabled)
BF L
191 L
60
0
120
Space Sensor Alarm Time (Minutes, 0 = Disabled)
C2 H
194 H
0
0
255
Intelli-Start Recovery Time (Minutes, 0 = Disabled)
C3 H
195 H
-
-
-
ASCD Timer For Compressor #1 High BYTE
C3 L
195 L
-
-
-
ASCD Timer For Compressor #1 Low BYTE (Seconds,
Counts Down)
C4 H
196 H
-
-
-
ASCD Timer For Compressor #2 High BYTE
C4 L
196 L
-
-
-
ASCD Timer For Compressor #2 Low BYTE (Seconds,
Counts Down)
C5 H
197 H
-
-
-
ASCD Timer For Compressor #3 High BYTE
C5 L
197 L
-
-
-
ASCD Timer For Compressor #3 Low BYTE (Seconds,
Counts Down)
C6 H
198 H
-
-
-
ASCD Timer For Compressor #4 High BYTE
C6 L
198 L
-
-
-
ASCD Timer For Compressor #4 Low BYTE (Seconds,
Counts Down)
C7 H
199 H
0
-
-
Compressor #1 Minimum Run Timer High BYTE (Seconds,
Counts Down)
C7 L
199 L
0
-
-
Compressor #1 Minimum Run Timer Low BYTE (Seconds,
Counts Down)
C8 H
200 H
0
-
-
Compressor #2 Minimum Run Timer High BYTE (Seconds,
Counts Down)
C8 L
200 L
0
-
-
Compressor #2 Minimum Run Timer Low BYTE (Seconds,
Counts Down)
C9 H
201 H
0
-
-
Compressor #3 Minimum Run Timer High BYTE (Seconds,
Counts Down)
C9 L
201 L
0
-
-
Compressor #3 Minimum Run Timer Low BYTE (Seconds,
Counts Down)
CA H
202 H
0
-
-
Compressor #4 Minimum Run Timer High BYTE (Seconds,
Counts Down)
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...