Page 64
Fig. Maximum pulse frequency for a minimum
pulse length of 50ms.
2.) Specify minimum pulse length
The UMG96S can output meter pulses with a
frequency of up to 10Hz.
In this example the data collector can record
meter pulses with frequencies of up to 50Hz.
The minimum pulse length of the UMG96S is
set to 50ms.
Minimum pulse length Add 010 = 50
Example: Programming the pulse output
The UMG96S is to measure measure the ac-
tive power demand in a sub-distribution and for-
warded to a data collector via the pulse output.
The sub-distribution supplies consumers which
together require a maximum 400kW active
power. The data collector can record pulse fre-
quencies up to 50Hz.
The
pulse output
, the
minimum pulse length
and the
pulse value
must be programmed at
the UMG96S.
Input/Output 2 (003)
Pulse output Wq (003 = 0)
Digital output
(003 = 1)
Analog output (003 = 2)
Digital input
(003 = 3.5)
Remote profibus (003 = 4)
Input/Output 1 (002)
Pulse output Wp (002 = 0)
Digital output
(002 = 1)
Analog output (002 = 2)
Digital input
(002 = 3.5)
Remote profibus (002 = 4)
12
13
11
UMG96S
+
1.) Select pulse output
Assign terminal 12 the pulse output function.
Input/Output 1 Add 002=0
Fig.: Connection example for wiring terminals
11 to 13 as pulse output.
+
-
230V AC
24V DC
External
Operating voltage
+24V=
11
12
13
UMG96S
Switching and pulse outputs
1.5k
Data
collector
Pulse
50ms
Interpulse
period
50ms
100ms => 10Hz
Minimum pulse length