Page 61
A maximum voltage of 2V is applied.
A voltage larger than 20V is applied.
Status displays
The status of the switching inputs and outputs
is denoted in the UMG96S’s display by circular
symbols.
Statuses at the digital input:
Statuses of a digital output:
A current <1mA can flow.
A current of up to 5mA can flow.
L1
L2
L3
K1
K2
Status at terminal 12
Status at terminal 13
The status of the digital input is not defined for
voltages within the range from 2V to 20V.