Page 78
Add
Name
Adjust.. range
Type Units Default
040
Comparator 2C, measured value
0 .. 999
INT 6)
041
Comparator 2C, minimum on-time
1 .. 899
INT
Sec.
1
042
Comparator 2C, operator
0, 1
CHAR 4)
0
043
Gate the results of the comp. (0,1,2)
0, 1
CHAR 1)
-
0
044
Invert result of logic oper. comp (0,1,2).
0, 1
CHAR 2)
-
0
045
Gate the results of the comp. (3,4,5)
0, 1
CHAR 1)
-
0
046
Invert result of logic oper. comp (3,4,5).
0, 1
CHAR 2)
-
0
047
Measured value for analog output 1
0 .. 999
INT
0
048
Analog output 1, 20mA
-999999999 ..
999999999
LONG
0
050
Analog output 1, 4mA
-999999999 ..
999999999
LONG
0
052
Measured value for analog output 2
0 .. 999
INT
0
053
Analog output 2, 20mA
-999999999 ..
999999999
LONG
0
055
Analog output 2, 4mA
-999999999 ..
999999999
LONG
0
056
Data recording
0 .. 15
CHAR
-
0
057
Averaging time, for I
0 .. 6
CHAR 3)
-
0
058
Averaging time, for P
0 .. 6
CHAR 3)
-
0
059
Change time
0 .. 60
CHAR
Sec.
0
060
Display profile
0 .. 3
CHAR
-
0
0 .. 2 = Pre-assigned displays profiles
3 = Freely selectable displays profiles
061
Display change profile
0 .. 3
CHAR
-
0
0 .. 2 = Pre-assigned display change
profiles
3 = Freely selectable display change
profiles
062
Interface selection
0, 1, 2
CHAR
-
0
0 = Autom interface recognition
1 = RS232
063
System frequency
0, 1, 2
CHAR
-
0
0 = System frequency from phase L1
1 = 50Hz
2 = 60Hz
064
Comparator 1A, lead time
1 .. 899
INT
Sec.
0
065
Comparator 1B, lead time
1 .. 899
INT
Sec.
0
066
Comparator 1C, lead time
1 .. 899
INT
Sec.
0
067
Comparator 2A, lead time
1 .. 899
INT
Sec.
0
068
Comparator 2B, lead time
1 .. 899
INT
Sec.
0
069
Comparator 2C, lead time
1 .. 899
INT
Sec.
0
070
Modem mode (0 = no, 1 = yes)
0, 1
CHAR
-
0
071
HT/LT switchover, (0 = HT, 1 = LT)
0, 1
CHAR
-
0
1) 0 = OR, 1 = AND
2) 0 = do not invert, 1 = invert
3) 0 = 5 sec, 1 = 10 sec, 2 = 30 sec, 3 = 60 sec, 4 = 300 sec, 5 = 480 sec, 6 = 900 sec
Parameter list Part 2
Содержание UMG 96S 24V
Страница 9: ...Page 9 ...