Page 79
Add
Name
Adjust. range
Type
Units Default
600
Current transformer, primary3)
1 .. 10000
INT
A
5
601
Current transformer, secondary3)
1 .. 5
INT
A
5
602
Voltage transformer, primary3)
100 .. 60000
INT
V
4001)
603
Voltage transformer, secondary3)
100 .. 400
INT
V
4001)
604
Measured value displays profile, current
2)
STRING1
-
-
605
Display change profile, current
2)
STRING1
-
-
700
Date and time
2)
STRING1
-
-
701
Clock option, yes=1, no= 0
read only
CHAR
-
-
702
Ring buffer store, data rec. num., read add
read only
INT
-
-
703
Ring buffer store option, yes=1, no= 0
read only
CHAR
-
-
800
Write in EEPROM
0 .. 4
CHAR
-
0
Bit 1 = 1, write calibration data.
Bit 2 = 1, write programming data.
Bit 4 = 1, write counter.
Bit 8 = 1, write min - max values.
911
Serial number
read only
LONG
-
######
913
Software release
read only
INT
-
###
914
Hardware configuration
read only
INT
-
###
1) In the 300V standard version: 400V; In the 150V special version: 100V.
2) These values can only be read and written using the PC software GridVis.
3) The parameters for the current and voltage transformer values can only be read at the
UMG96S.
Parameter list Part 3
Important!
For several parameters, only the PC software
GridVis can utilise the maximum adjustment
range. Only values up to 999999 can be set at the UMG96S.